20 A MCB on 2.5 sq mm
2.5 sq mm carries 18 A in conduit. With a 20 A MCB, the wire can run hot for hours without a trip. Use 16 A on 2.5, or move up to 4 sq mm for 20 A.
The amps printed on your AC's name plate decide which row you are in, not the tonnage. And every AC gets its own line from the board, with nothing else on it.
Tonnage tells you how much cooling an AC gives. The wire has to carry the current the AC draws, and that changes with the brand, the star rating and whether it is an inverter model. The plate gives the exact figure.
Why tonnage can't tell you the wire. A "ton" is a measure of cooling: one ton of refrigeration is about 3.5 kW of heat taken out of the room. How much electricity the AC uses to do that depends on its compressor and star rating. Two 1.5-ton ACs from different makers can print quite different amps.
The MCB's job is to switch off before the wire gets too hot. So the MCB has to be smaller than what the wire can carry, and big enough that the AC runs all night without tripping it.
| Plate current | Wire, MCB and connection |
|---|---|
| ≤ 12 A | 2.5 sq mm × 3 · 16 A C-curve MCB16 A socket with its switch. Most 1-ton and 1.5-ton home splits. |
| 12–16 A | 4 sq mm × 3 · 20 A C-curve MCBDirect point through a 20 A switch, no socket. Check twice on 2-ton and old fixed-speed units. |
| Over 16 A | Send us the plate firstThis needs a heavier line than a normal house AC point. We'll work it out with your electrician. Rare in homes here. |
| Any AC | Never 1.5 sq mmIt carries 13 A in conduit (Classo+) and is meant for light and fan circuits. See wire amps chart. |
What electricians here run. For a 1-ton or 1.5-ton split, most run 2.5 sq mm; some run 4 sq mm for every AC point to be safe for a bigger AC later. Both are right when the plate fits. 2.5 sq mm is the minimum: if your electrician suggests 1.5 sq mm "because it's only 1 ton", say no. If the board-to-AC run is long, use the calculator below: past about 30 m, 4 sq mm is often worth it.
An AC's compressor is a motor. Every time it starts, it pulls a short burst of current much higher than its running current. The MCB has to tell that harmless burst apart from a real fault.
A B-curve MCB trips at once when current reaches 3 to 5 times its rating. A starting compressor can get there, so the MCB drops every time the AC kicks in. A C-curve waits until 5 to 10 times its rating. It lets the start through and still trips on a short circuit. B-curve is for lights and fans.
On 2.5 sq mm (18 A in conduit) the MCB is 16 A. On 4 sq mm (24 A in conduit) it is 20 A. A 20 A MCB on 2.5 sq mm is the most common mistake we see: between 18 and 20 A the wire runs hot inside the wall and nothing trips.
If a correct 16 A C-curve keeps tripping, something is wrong: a shared line, a loose joint, or an AC drawing more than its plate. Swapping in a 20 A only hides it. See MCB tripping again and again.
V-Guard Elegna is 10 kA, single pole from 6 to 63 A, B and C curve, IS/IEC 60898-1. We keep the 20 A C-curve and 10 A B-curve on the shelf. The 16 A C-curve for a 2.5 sq mm AC line is ordered for you: ask on WhatsApp for the time it takes. Elegna MCB · B vs C curve
On a 2.5 sq mm line with a 16 A MCB: a 16 A socket with its own switch, next to where the indoor unit will hang. You can switch it off and pull the plug when the AC is serviced. Our Torio 6/16 A socket takes the AC's big plug, and the 16 AX switch goes beside it.
On a 4 sq mm line with a 20 A MCB: a direct point, where the wire goes through a 20 A switch straight to the AC's lead, with no plug. A 16 A socket shouldn't sit on a 20 A circuit, because the MCB would let the socket run past its own rating.
Never a 6 A socket, and never a 3-pin adapter. Their contacts are made for a TV or a charger. On an AC they heat up and scorch, usually in the first summer. More in 6 A vs 16 A switch and socket.
One MCB, one AC, one run of wire. Don't take the AC from the room's light and fan circuit, the room's sockets, the geyser line or another AC's line. Two ACs means two lines and two MCBs. Building new? Mark the AC points before the walls are chased, so the conduit goes in then: AC point before plaster.
The green earth wire is the same size as the other two: 2.5 sq mm on a 2.5 line, 4 sq mm on a 4 line. The standard wiring rule keeps earth the same size as the phase wire up to 16 sq mm. The AC's metal body and outdoor unit sit on it. It only helps if the house earthing is sound: earthing basics.
A V-Guard VGMW 500 Plus is rated 15 A for the whole house. Lights, fans, TV and fridge fit; an AC on top of them can push the total past 15 A. Take the AC line from the board before the stabiliser. Most inverter ACs list a wide working voltage in their manual. Read it before buying a separate one: stabiliser for an inverter AC.
Most of these are hidden in the wall. You find out in May, when the AC runs all night for the first time.
2.5 sq mm carries 18 A in conduit. With a 20 A MCB, the wire can run hot for hours without a trip. Use 16 A on 2.5, or move up to 4 sq mm for 20 A.
A light-fan circuit is thin wire behind a small B-curve MCB. The AC trips it, or worse, someone fits a bigger MCB on it. Run a new line from the board.
Small sockets and adapters aren't made for an AC's current. Use a 16 A socket on a 16 A line, or a direct point on a 20 A line.
B-curve trips instantly at 3 to 5 times its rating, which a compressor start can reach. Use C-curve, which waits until 5 to 10 times.
Run three wires, all the same size, and make sure the green one reaches a working earth at the board. A fault in the AC then trips the line instead of reaching you.
A twisted, taped joint is the weakest point on the line and heats under an AC's load. Pull one unbroken length from the board to the point. Measure first, so the coil covers it.
Put in the current from the name plate and how far the AC is from the board. You get the wire size, the MCB, the socket or point, the metres of each colour, and how much voltage the wire loses on the way.
Wire limits: V-Guard Classo+ in conduit. Voltage loss uses the standard maximum resistance for copper house wire (IS 8130: 7.98 Ω/km for 2.5 sq mm, 4.95 for 4 sq mm) and adds 1.5 m at each end for the board and the point. Price: Ask rate per 90 m coil, filled in from today's rate. Whole house: wiring calculator.
Prices are from our latest bill and change often. Please confirm today's rate on WhatsApp or call before buying.
V-Guard Classo+ 2.5 sq mm18 A in conduit · 90 m coil · for ACs up to 12 A₹ 3,211per 90 m 4 sq mm house wire24 A in conduit (Classo+) · for ACs 12–16 A · ordered for youAsk today's rateper 90 mAnything not on the shelf, we order for you; ask on WhatsApp for the time it takes. Today's price for every coil: wire price list.
Read the current on the AC's name plate. If it is 12 A or less, which is the usual case for a home split, run 2.5 sq mm copper wire (phase, neutral and earth) with a 16 A C-curve MCB and a 16 A socket. If it is above 12 A and up to 16 A, run 4 sq mm with a 20 A C-curve MCB and a direct point.
Only if the plate shows 12 A or less. Above that, use 4 sq mm and a 20 A C-curve MCB. A 2-ton AC is where the plate most often changes the answer, so read it before you buy the wire.
The wire decides. V-Guard Classo+ 2.5 sq mm carries 18 A in conduit, so it gets a 16 A MCB. A 20 A MCB goes only on 4 sq mm, which carries 24 A in conduit. Both must be C-curve.
No. 1.5 sq mm carries 13 A in conduit (Classo+), and it can't take the 16 A MCB and 16 A socket an AC point needs. It is for lights and fans. 2.5 sq mm is the minimum for any AC.
No. Every AC gets its own line from the board with its own MCB. Two ACs, two lines.
On a 2.5 sq mm line with a 16 A MCB, a 16 A socket with its switch, which lets you unplug the AC for servicing. On a 4 sq mm line with a 20 A MCB, a direct point through a 20 A switch. Never a 6 A socket or an adapter.
The same as the phase wire: 2.5 sq mm on a 2.5 line, 4 sq mm on a 4 line. The standard wiring rule keeps earth the same size as the phase up to 16 sq mm.
The rule doesn't change: go by the plate. Inverter ACs start more gently, but use the same wire, MCB and socket table above.
Home inverter and battery sets of the size most houses here have are planned for lights, fans, TV and the fridge, not an AC. Keep the AC line off the inverter circuit. See what runs on an inverter.