2.5 sq mm wire in Muzaffarpur: 16 A sockets, kitchen, geyser and small AC, 18 A in a pipe, 90 m coil
2.5 sq mm is the wire for sockets and heavier points. V-Guard Classo+ 2.5 sq mm carries 18 A in a wall pipe (22 A clipped in open air), so it takes a 16 A MCB, never 20 A. Use it for 16 A sockets, the kitchen, the geyser (16 A double-pole MCB) and a 1 ton or 1.5 ton split AC whose name plate says up to 12 A (16 A C-curve MCB). Over 12 A, take 4 sq mm.
Today's price on the wire price list
Put it on these, move size for those
Power circuits
- 16 A sockets: mixer, iron, cooler, washing machine (thick-pin plug).
- The kitchen line, on its own 16 A MCB.
- The geyser: its own line, 16 A double-pole MCB.
- A 1 ton or 1.5 ton split AC with name plate up to 12 A.
- A small water pump, sized from its name plate.
When 2.5 is wrong
- AC with name plate 12 to 16 A, or a long pump run: 4 sq mm, 20 A MCB.
- Lights, fans and 6 A sockets only: save the money, use 1.5 sq mm.
- Two heavy loads on one 2.5 line (geyser plus a socket line): split into two lines.
- MCB keeps tripping: find the load, never fit a bigger MCB: MCB tripping again and again.
Which size for every point in a house, side by side: 1.5 vs 2.5 sq mm wire.
The numbers for 2.5 sq mm Classo+
V-Guard prints a current figure for Classo+; most wire makers' pages print none. The full chart for every size is the wire amps chart.
| What | Figure | What it means |
|---|---|---|
| In a wall pipe | 18 A | The figure to use in a house; about 4,140 W at 230 V. |
| Clipped, open air | 22 A | Not for a house: even the bit near the board counts as in-pipe. |
| MCB in front | 16 A | Plan the load up to 3,680 W, about 3,600 W in practice. Never 20 A. |
| Strands × mm, overall width | 48 × 0.25 · 3.4 mm | Soft multi-strand; insulation 0.7 mm. |
| Max resistance | 7.98 Ω/km | The number to hold the wire to. |
| Copper in a 90 m coil | ~2.0 kg | Our own sum from the size, so the price follows copper. |
A 1 ton or 1.5 ton AC: read the plate, then pick
Most split ACs here are 1 ton or 1.5 ton. Read the amps on the name plate, then find the box below.
2.5 sq mm coils for your house
Like every size, 2.5 sq mm is bought as red, black and green: one coil of each is the smallest order. That is why a one-room house and a three-room house both come to three coils.
| House (single floor unless stated) | 2.5 sq mm coils | Wire used |
|---|---|---|
| 1 room, kitchen, bath | 3 | ~83 m |
| 2 rooms, kitchen, bath, AC, geyser, pump | 3 | ~218 m |
| 3 rooms, kitchen, 2 baths, AC, geyser, pump | 3 | ~238 m |
| Two floors, 2 rooms each | 6 | ~375 m |
| Three floors, 2 rooms each | 9 | ~693 m |
Usual practice with 10% spare, from our coil guide; your electrician's point list decides the final count. Counter: wiring calculator. Pipe for 2.5 sq mm runs is 25 mm: conduit pipes.
2.5 sq mm at our store, with today's price
Prices are from our latest bill and change often. Please confirm today's rate on WhatsApp or call before buying.
Classo+ 2.5 sq mmBlack · 90 m · sockets, kitchen, geyser, small AC₹ 3,211per coil Ultravolt SafePlus 2.5 sq mmUltraTech · 70 °C · low smoke · ordered for youAsk today's rateper coil Ultravolt GreenCore 2.5 sq mm95 °C · for geyser and kitchen lines · 90 m or 180 mAsk today's rateper coilEvery coil goes out on a GST bill. Other colours, other makes and any MCB rating we can order for you; ask on WhatsApp for the time it takes. All sizes in one place: wire price list. Delivery is charged separately; ask for the amount for your site (delivery).
Online, the amps for 2.5 sq mm run from 10 A to 25 A
We read what sites say about 2.5 sq mm on 18 Nov 2026. Here is the spread, and the figure we stand by.
| Source | Amps | MCB | Gap |
|---|---|---|---|
| NoBroker forum | 10 A | none | Lower than V-Guard's figure for 1.5 sq mm; no MCB. |
| Joca Cable blog | 20–25 A | 20 A | Foreign standards (IEC, NEC, BS); 20 A is above V-Guard's 18 A pipe figure. |
| Polycab product page | none | none | MRP only, no amps and no circuit advice. |
| Tashya (V-Guard Classo+) | 18 A pipe · 22 A clip | 16 A | Pipe figure, MCB, AC, geyser, coils and colours on one page. |
Short answers
What is the 2.5 sq mm wire price in Muzaffarpur?
Today's price for a 90 m coil of Classo+ 2.5 sq mm, with GST, is on the wire price list, updated each morning. Divide by 90 for the price per metre. The black coil is on the shelf; other colours we order.
How many amps does 2.5 sq mm wire carry, and which MCB?
V-Guard's Classo+ table: 18 A in a wall pipe, 22 A clipped in the open. Use 18 A, with a 16 A MCB. Never 20 A: between 18 and 20 A the wire heats inside the wall and a 20 A MCB does not trip.
Can a geyser run on 2.5 sq mm?
Yes: its own 2.5 sq mm line from the board, with a 16 A double-pole MCB, as CPWD's wiring specification recommends for water heaters. Do not share it with a socket line. Geyser wire in detail.
Is 2.5 sq mm enough for a 1.5 ton AC?
Go by the name plate. Up to 12 A: 2.5 sq mm and a 16 A C-curve MCB. 12 to 16 A: 4 sq mm and 20 A. Above 16 A, send us the plate. The arithmetic: wire size for an AC.
Can I put a 20 A MCB on 2.5 sq mm?
No. 20 A goes only on 4 sq mm. Some websites suggest 20 A for 2.5 sq mm; that is above V-Guard's 18 A pipe figure.
How much can one 2.5 sq mm kitchen line carry?
With a 16 A MCB, plan up to 3,680 W in all on that line. A geyser or oven on the same wall should get its own line.
Looks after wires, switchgear, inverters and pumps at our Rewa Road store, Muzaffarpur. The amp figures are V-Guard's own, checked on 18 Nov 2026. Where makers disagree, this page says so and takes the safer figure.
Where the numbers come from
- V-Guard, Classo+ triple layer insulation wire: 18 A in a wall pipe and 22 A clipped for 2.5 sq mm, 48 × 0.25 mm strands, 3.4 mm overall, 0.7 mm insulation, 7.98 Ω/km, 70 °C, 1100 V.
- MCB at or below the in-pipe figure, earth the same size as phase (IS 732), coil counts and pipe lengths: our own wire amps chart and coil guide, linked above.
- Geyser on a 16 A double-pole MCB: CPWD's wiring specification, as cited in our coil guide.
- Other sites read on 18 Nov 2026: NoBroker, Joca Cable, Polycab.
- Store facts: our own shelf at Rewa Road; colours as on our last supplier bill.
Tell us your points, we'll tell you the coils
Send the number of sockets, ACs and geysers, with the AC name-plate amps. We reply with the coils by size and colour, and one price for the lot.