House wire: which size goes where, and which MCB goes with it

The short answer
  1. Lights, fans 1–1.5
  2. Sockets 2.5
  3. AC, geyser 2.5 / 4
  4. Mains 6

Sizes are in sq mm. Pick the size by the circuit, then put the MCB below what the wire carries. 2.5 sq mm in a wall pipe gets a 16 A MCB only; 20 A goes on 4 sq mm. The earth wire is the same size as the phase wire.

18 A
2.5 sq mm in a pipeSo 16 A MCB, never 20 A.
90 m
One coilClasso+ and Ultravolt both come in 90 m coils.
2
Makes we sellV-Guard Classo+ on the shelf, UltraTech Ultravolt to order.
Five sizes, what each carries
Five wire sizes, copper to scale, with amps and MCBCut ends of 1, 1.5, 2.5, 4 and 6 sq mm wire. Each shows the amps it carries in a wall pipe and the MCB in front of it. 1 sq mmcarries 11 A · MCB 6 / 10 ASwitchboard to one light orfan point1.5 sq mmcarries 13 A · MCB 10 ALight and fan circuits, 6 Asockets2.5 sq mmcarries 18 A · MCB 16 A16 A sockets, geyser, AC upto 12 A4 sq mmcarries 24 A · MCB 20 AAC of 12–16 A, long pump run6 sq mmcarries 31 A · MCB 25 AMain line from the meter Copper drawn to scale; insulation is schematic.
Amps in a wall pipe from the V-Guard Classo+ table (6 sq mm from Ultravolt SafePlus). MCB is ours, at or below the wire.
Pick fast

What is the wire for?

The whole house

From the meter to each line

One board, four kinds of line
Which size goes where, from the meter to each lineMeter, 6 sq mm main, board, then lights and fans on 1.5, sockets and geyser on 2.5 with 16 A, AC on 2.5 or 4, and the earth wire the same size as phase.Meter6 sq mm mainBoard: DP main + RCCB + MCBsLights, fans1.5B10Sockets2.516 AGeyser2.516 AAC2.5 / 4C16 / C20Earth wire: same size as the phase wire on every line
Every line has its own MCB. An AC gets a line of its own. The 4 sq mm AC line needs a 20 A C-curve MCB.

Most houses use only three or four sizes. How many coils each takes, floor by floor, is on coils for a house; this page only helps you choose.

Earth wire: same size as the phase wire, on every line. A wire is bought in sets of three coils: red for phase, black for neutral, green for earth. The red and black coils of 1 and 1.5 sq mm are on our shelf; green and every other colour we can order for you.

Not sure about a size? Click a size to read its own page:

The one rule

The MCB sits below the wire, never above

Wire amps against MCB
The MCB always sits below what the wire carriesBars show amps each size carries in a wall pipe; the green mark is the MCB. A 20 A MCB on 2.5 sq mm, marked red, is past the wire's 18 A. SQ MM · AMPS IN A WALL PIPE1wire 11 AMCB 6–101.5wire 13 AMCB 102.5wire 18 AMCB 164wire 24 AMCB 206wire 31 AMCB 25✕ 20 A
Green: the MCB we fit. Red, dashed: a 20 A MCB on 2.5 sq mm, past the wire’s 18 A.

The MCB is there to protect the wire. If it is bigger than the wire can carry, the wire heats inside the wall and the MCB does not trip. That is why 2.5 sq mm gets 16 A only, and 20 A is for 4 sq mm.

B-curve or C-curve, the 30 mA RCCB and the board layout are on which MCB for which load. If an MCB trips again and again, read MCB tripping before changing it for a bigger one.

Our wire

Two makes, and what goes with them

Every coil comes on a GST bill. Anything not on the shelf (4 and 6 sq mm, other colours, any Ultravolt range) we can order for you; ask on WhatsApp for the time it takes. Price per coil today: wire price list.

Questions people ask us

Short answers

Which wire for the whole house, in one line?

1.5 sq mm for lights and fans, 2.5 sq mm for sockets, 2.5 or 4 sq mm for each AC and the geyser (by the amps on the name plate), and 6 sq mm for the main line from the meter. Each line has its own earth wire of the same size.

Can I put a 20 A MCB on 2.5 sq mm wire?

No. In a wall pipe 2.5 sq mm carries 18 A (V-Guard Classo+ table). A 20 A MCB lets the wire run hot between 18 and 20 A and never trips. 2.5 sq mm gets a 16 A MCB; 20 A goes only on 4 sq mm.

How thick should the earth wire be?

The same size as the phase wire on that line (IS 732). So a 2.5 sq mm socket line has a 2.5 sq mm earth wire, not a thinner one.

Classo+ or Ultravolt?

For ordinary lights, fans and sockets they are equals, so buy the one that costs less per coil that day. Ultravolt’s GreenCore (95 °C) is the step up for AC, geyser and kitchen lines, and 6 sq mm is Ultravolt only. The full comparison is on its own page.

Is every size on your shelf?

Classo+ 0.75 (green), 1 (red, black), 1.5 (red, black) and 2.5 sq mm (black) are on the shelf. Everything else, including 4 and 6 sq mm, other colours and all Ultravolt, we can order for you; ask on WhatsApp for the time it takes.

What does a coil cost?

Today’s price for every size and range is posted each morning on the wire price list, with GST on the bill.

Sashikesh Kumar
Diploma in Electrical, Tashya Ventures

Electrical counter at our Reva Road store, Muzaffarpur. Every figure on this page was checked against the makers’ tables on 14 Nov 2026. Where makers’ amp figures differ, we use the lower, safer one.

Where the numbers come from

  1. V-Guard, Classo+ product page: 99.97% copper, FR PVC, 70 °C, 1100 V, 90 m; current table in conduit and clipped (0.75: 6/7 A, 1: 11/12, 1.5: 13/16, 2.5: 18/22, 4: 24/29).
  2. Ultravolt (UltraTech wires and cables), SafePlus product page: six sizes 0.75 to 6 sq mm; the 6 sq mm figure of 31 A in conduit is its 70 °C rating.
  3. IS 732 (wiring installations): earth conductor the same size as the phase conductor in these small sizes. The MCB at or below the wire's amps is standard practice, as on our wire amps chart.
  4. Owner's counter figures: 2.5 sq mm gets a 16 A MCB only; 4 sq mm 20 A at most; AC name-plate rule (up to 12 A, 12 to 16 A, above 16 A).

Send us your circuits

Tell us the lights, sockets, ACs and geyser, and we will send back sizes, coils and MCBs, with today’s price.