How many amps does 1, 1.5, 2.5 and 4 sq mm wire carry? With the right MCB for each

The short answer · V-Guard Classo+, in a wall pipe
1.5 sq mm
13 Awire carries
10 AMCB
2.5 sq mm
18 Awire carries
16 AMCB
4 sq mm
24 Awire carries
20 AMCB

Almost every wire in a house runs inside a pipe in the wall, so read the in-pipe figure. The MCB always sits below what the wire carries, so it trips before the wire gets hot. 1 sq mm carries 11 A and 0.75 sq mm 6 A.

2.5 sq mm gets a 16 A MCB, never 20 A. Between 18 and 20 A the wire cooks inside the wall and a 20 A MCB never trips. 20 A goes only on 4 sq mm.
Amps each size carries, and its MCB
Current rating of V-Guard Classo+ wire by size Five rows. 0.75 sq mm: 6 A in a pipe, 7 A in open air, MCB 6 A. 1 sq mm: 11 and 12 A, MCB 6 or 10 A. 1.5 sq mm: 13 and 16 A, MCB 10 A. 2.5 sq mm: 18 and 22 A, MCB 16 A. 4 sq mm: 24 and 29 A, MCB 20 A. In every row the red MCB line sits at or inside the dark in-pipe bar. In a wall pipe Open air, clipped MCB 0 A10 A20 A30 A 0.7511.52.54 sq mmsq mmsq mmsq mmsq mm 611131824 712162229 6 A6 or 10 A10 A16 A20 A The red line never crosses the end of the dark bar.
Figures: V-Guard Classo+ product page, two wires of one single-phase circuit. MCB column: standard practice, the MCB at or below the in-pipe figure.
The full chart

Size, amps, watts and MCB on one table

Most wire makers' sites show sizes and colours but no current figure at all. V-Guard prints one for Classo+, so this is the table we work from at the counter.

SizeIn a wall pipeClipped, open airWire limit at 230 VMCB in frontPlan the load up toUsed for
0.756 A7 A1,380 W6 A1,380 WShort drops, bell and control wiringnot a house circuit
1.011 A12 A2,530 W6 / 10 A1,380 / 2,300 WLight and fan pointsfrom the switchboard to the point
1.513 A16 A2,990 W10 A2,300 WLight and fan circuits, 6 A socketsB-curve MCB
2.518 A22 A4,140 W16 A3,680 W16 A sockets, geyser, AC up to 12 A, pumpnever a 20 A MCB
4.024 A29 A5,520 W20 A4,600 WAC of 12–16 A, long pump runs, feed to a sub-board

Two watt columns, on purpose. "Wire limit" is the in-pipe amps × 230 V. But the MCB trips first, so the load you can really put on a circuit is the MCB × 230 V. Plan with the last column. A 2.5 sq mm socket line runs about 3,600 W, not 4,100.

B or C curve. Same rating, different start tolerance: B-curve for lights, fans, sockets and a geyser; C-curve for anything with a motor or compressor (AC, pump, fridge line), so the start surge doesn't trip it. More in which MCB for which load and B vs C curve.

Why two figures

The same wire carries less inside a pipe

Current heats the wire. The rating is simply the current at which the wire reaches its safe temperature, and that depends on how fast the heat can leave.

Heat in a pipe and in open air Left: a cross-section of a plastered wall with a PVC pipe holding two wires; red heat arrows curl back inside the pipe. 2.5 sq mm carries 18 A here. Right: the same wire clipped on the wall surface; heat arrows rise away into the air. It carries 22 A here. Pipe in plaster heat stays in 18 A Clipped, open air heat leaves 22 A same 2.5 sq mm
Classo+ 2.5 sq mm: 18 A in conduit, 22 A unenclosed (V-Guard). Classo+ is made to withstand 70 °C.

Use the pipe figure in a house

In a Bihar house almost every run is in a pipe in the wall or the slab. So the first column is the one that applies, even for the short bit that is clipped near the board.

Our summers make it count

A west wall or a roof slab in May is already hot before any current flows. The wire starts warm and has less room to heat. That is one more reason never to push a wire to its open-air figure.

Don't crowd one pipe

V-Guard's figures are for the two wires of one circuit. Usual practice: give each circuit its own run of pipe where you can, and don't pull extra circuits through a pipe that is already full. More wires in one pipe means more heat in one place.

Which type of wire to buy in the first place (FR, FRLS, HFFR) is a separate question: FR vs FRLS vs HFFR · types of wire for a home.

The one rule

Load ≤ MCB ≤ wire

The MCB is there to protect the wire, not the appliance. So it is chosen from the wire's amps, and the appliance only has to fit under it.

Load, MCB and wire in order Right way: a 2 kW geyser drawing 8.7 A, under a 16 A MCB, under 2.5 sq mm wire carrying 18 A. Wrong way: the same geyser and wire with a 20 A MCB; 20 is more than 18, so the wire can overheat before the MCB trips. RIGHT LOAD8.7 A2 kW geyser ≤ MCB16 Atrips first ≤ WIRE18 A2.5 sq mm WRONG LOAD8.7 A2 kW geyser ≤ MCB20 Atoo big > WIRE18 A2.5 sq mm Between 18 and 20 A the wire heats and the 20 A MCB stays on.
The geyser works fine either way. That is why the wrong MCB goes unnoticed until a socket or a joint fails on a busy day.

How to read it

  • Wire first. Find the in-pipe amps of the wire on that circuit from the chart.
  • MCB next. Pick the standard MCB at or just below it: 1.5 → 10 A, 2.5 → 16 A, 4 → 20 A.
  • Load last. Add up everything on the circuit. It must stay under the MCB, with room to spare.
  • Load too big? Move up a wire size and its MCB together, or split the load into two circuits. Never fit a bigger MCB on the same wire.
  • MCB trips often? It is doing its job. Find the cause in MCB tripping again and again.

Room by room, which circuit gets which MCB: which MCB for which load. The V-Guard Elegna MCB we sell comes from 6 to 63 A in B and C curve.

Check your own load

Put in the name plate, get the wire and MCB

Read the watts or the amps off the appliance's name plate. For an AC or a motor, use the amps: watts ÷ 230 understates what they really draw.

Two things on one circuit? Add their watts (or amps) first. 1 kW = 1,000 W. For a motor plate in HP only, 1 HP = 746 W of output; the input is higher, so read the amps.

What it needs

Current at 230 V——
Wire——
MCB——
—
Send this on WhatsApp

Wire limits: V-Guard Classo+ in a pipe. AC and motor lines follow our AC rule: up to 12 A on 2.5 sq mm with 16 A C-curve, 12–16 A on 4 sq mm with 20 A C-curve, above that send us the plate. Long run to a boring or an outhouse: check the drop in the wiring calculator. Price: Ask rate.

Three worked examples

A 1.5-ton AC, a 2 kW geyser and a 1 HP motor

The three lines people ask us about most, worked with the chart. Each has its own detailed page; this is the arithmetic.

1.5-ton split AC

Plate amps decide, not the tonnage
  1. Read the current on the plate. Most 1 and 1.5-ton home splits show 12 A or less.
  2. 12 A is well inside 2.5 sq mm (18 A), so the wire is 2.5 sq mm × 3 (phase, neutral, earth).
  3. MCB at or below 18 A: 16 A. C-curve, so the compressor start doesn't trip it.
  4. Plate above 12 A: 4 sq mm and 20 A C-curve. Above 16 A: send us the plate.
2.5 sq mm16 A C-curveown line

Socket, earth and the stabiliser question: wire size for an AC.

2 kW geyser

Small current, long hours
  1. 2,000 W ÷ 230 V = about 8.7 A.
  2. 1.5 sq mm (13 A) would carry it on paper, but its MCB is only 10 A and a geyser runs for an hour at a stretch in winter. Use 2.5 sq mm (18 A).
  3. MCB at or below 18 A: 16 A. B-curve is fine for a heater.
  4. Own line from the board, with a 16 A switch and socket or a direct point.
2.5 sq mm16 A B-curveown line

Bathroom details: wire size for a geyser.

1 HP water motor

Start surge and a long run
  1. A single-phase 1 HP motor runs at about 8 A (standard figure; your plate decides) and pulls 2 to 3 times that for a moment at start.
  2. 2.5 sq mm (18 A) leaves room for the surge and the evening low voltage. 1.5 sq mm doesn't.
  3. MCB at or below 18 A: 16 A, C-curve for the start.
  4. Boring more than about 50 m away: 4 sq mm, to keep the voltage up at the motor.
2.5 sq mm16 A C-curve4 sq mm if far

Run length and the drop: wire size for a motor or pump.

Before the wire goes in the wall

Is it really 2.5 sq mm? Check it at the counter

The chart only holds if the wire is the size printed on it. Two checks anyone can do with the coil in hand.

Cut ends of Classo+ wire, drawn to scale with each other Four cut wire ends drawn to the same scale. 1 sq mm: 32 strands, about 2.5 mm across. 1.5 sq mm: 30 strands, 2.8 mm. 2.5 sq mm: 48 strands, 3.4 mm. 4 sq mm: 56 strands, 4.0 mm. 11.52.54 32 strands2.5 mm 30 strands2.8 mm 48 strands3.4 mm 56 strands4.0 mm Across the outside, insulation included
Strand count and overall diameter: V-Guard Classo+ table. All four drawn to one scale, about 12 times life size, so they compare truly.

Two checks

  • Read the print on the insulation: size, brand and the BIS mark run along the whole length. A coil of Classo+ also carries V-Guard's "90 m assured" seal.
  • Count the strands at a cut end: 1.5 sq mm Classo+ has 30 strands of 0.25 mm, 2.5 sq mm has 48 of 0.25 mm. Fewer strands than that is a thinner wire, whatever the label says.
  • Thin-for-its-label wire is the usual reason a "2.5 sq mm" line runs hot on a load the chart says is fine. More on spotting it: real or fake wire.
  • The earth wire is the same size as the phase wire (IS 732), so a 2.5 sq mm line needs three 2.5 sq mm wires. Colours: phase, neutral, earth.

How many coils for a whole house, size by size: wire coils for a house.

What we see go wrong

Four mistakes the chart prevents

20 A MCB on 2.5 sq mm

You see: nothing, until a socket browns

The wire carries 18 A in a pipe. A 20 A MCB lets it run hot for hours. On 2.5 sq mm the MCB is 16 A.

1.5 sq mm on a power socket

You see: a warm plate, a melted plug

A 16 A socket on 1.5 sq mm (13 A) is a socket asking for more than its wire. 16 A sockets go on 2.5 sq mm.

Reading the open-air figure

You see: fine on paper, hot in the wall

22 A is for 2.5 sq mm clipped in open air. Buried in a pipe it is 18 A. Wires in a house are in pipes.

Bigger MCB to stop tripping

You see: the tripping stops, the heating starts

A trip means the load is too big for the wire or something is faulty. Find out which; don't raise the MCB.

Questions people ask us

Short answers

How many amps can 1.5 sq mm wire carry? (1.5 mm taar kitna load leta hai)

V-Guard Classo+ 1.5 sq mm carries 13 A in a pipe in the wall and 16 A clipped in open air. In a house use 13 A, and put a 10 A MCB in front of it. It is the wire for lights and fans.

How many watts can 2.5 sq mm wire carry?

In a wall pipe, 2.5 sq mm Classo+ carries 18 A, about 4,140 W at 230 V. Its MCB is 16 A, so plan the load on that circuit to stay under 16 A, about 3,680 W.

Which MCB for 2.5 sq mm wire?

16 A, never 20 A. The wire carries 18 A in a pipe; a 20 A MCB would let it run between 18 and 20 A without tripping. 20 A goes only on 4 sq mm. C-curve for an AC or a motor, B-curve for sockets and a geyser.

Why is the rating in a pipe lower than clipped?

Heat. In open air the heat leaves the wire; in a pipe buried in plaster it stays, so the wire reaches its safe temperature at a lower current.

Can I use 1.5 sq mm wire for an AC?

No. It carries 13 A in a pipe and takes at most a 10 A MCB, which the AC's start trips. An AC needs 2.5 sq mm with a 16 A C-curve MCB, or 4 sq mm with 20 A if the plate shows more than 12 A. See wire size for an AC.

What about 6 sq mm wire?

V-Guard's Classo+ table stops at 4 sq mm, so we don't print a figure for 6 sq mm here. If a load needs more than 4 sq mm, send us the name plate and the run length; we read the rating off the data sheet of the exact wire we order for you.

Is copper the same as aluminium on this chart?

No. Every figure here is for copper house wire. Aluminium of the same size carries less. See copper vs aluminium wire.

Sashikesh Kumar
Diploma in Electrical, Tashya Ventures

Looks after wires, switchgear, inverters and pumps at our Reva Road store, Muzaffarpur. Every amp figure on this page was checked against V-Guard's own Classo+ table on 13 Nov 2026. Where a rule could go two ways, the page gives the safer one.

Where the numbers come from

  1. V-Guard, Classo+ house wire product page: current for two cables, single phase, in conduit / unenclosed: 0.75 sq mm 6 / 7 A, 1 sq mm 11 / 12 A, 1.5 sq mm 13 / 16 A, 2.5 sq mm 18 / 22 A, 4 sq mm 24 / 29 A; strands 32/0.2, 30/0.25, 48/0.25, 56/0.3; overall diameter 2.5, 2.8, 3.4, 4.0 mm; made to withstand 70 °C; "90 m assured" seal.
  2. V-Guard, Elegna MCB technical specification: 6 to 63 A, B and C curve, 10 kA, IS/IEC 60898-1.
  3. IS 732 wiring code (standard figure): earth conductor the same size as the phase conductor up to 16 sq mm.
  4. Standard figures: single-phase supply 230 V; watts ÷ 230 = amps for heaters; 1 HP = 746 W; single-phase 1 HP motor about 8 A running, 2 to 3 times at start.