How many amps does 1, 1.5, 2.5 and 4 sq mm wire carry? With the right MCB for each
Sashikesh Kumar, Diploma in Electrical · checked against V-Guard's own table, 13 Nov 2026
The short answer · V-Guard Classo+, in a wall pipe
1.5 sq mm
13 Awire carries
10 AMCB
2.5 sq mm
18 Awire carries
16 AMCB
4 sq mm
24 Awire carries
20 AMCB
Almost every wire in a house runs inside a pipe in the wall, so read the in-pipe figure. The MCB always sits below what the wire carries, so it trips before the wire gets hot. 1 sq mm carries 11 A and 0.75 sq mm 6 A.
2.5 sq mm gets a 16 A MCB, never 20 A. Between 18 and 20 A the wire cooks inside the wall and a 20 A MCB never trips. 20 A goes only on 4 sq mm.
Amps each size carries, and its MCB
Figures: V-Guard Classo+ product page, two wires of one single-phase circuit. MCB column: standard practice, the MCB at or below the in-pipe figure.
The full chart
Size, amps, watts and MCB on one table
Most wire makers' sites show sizes and colours but no current figure at all. V-Guard prints one for Classo+, so this is the table we work from at the counter.
AC of 12–16 A, long pump runs, feed to a sub-board
Two watt columns, on purpose. "Wire limit" is the in-pipe amps × 230 V. But the MCB trips first, so the load you can really put on a circuit is the MCB × 230 V. Plan with the last column. A 2.5 sq mm socket line runs about 3,600 W, not 4,100.
B or C curve. Same rating, different start tolerance: B-curve for lights, fans, sockets and a geyser; C-curve for anything with a motor or compressor (AC, pump, fridge line), so the start surge doesn't trip it. More in which MCB for which load and B vs C curve.
Why two figures
The same wire carries less inside a pipe
Current heats the wire. The rating is simply the current at which the wire reaches its safe temperature, and that depends on how fast the heat can leave.
Classo+ 2.5 sq mm: 18 A in conduit, 22 A unenclosed (V-Guard). Classo+ is made to withstand 70 °C.
Use the pipe figure in a house
In a Bihar house almost every run is in a pipe in the wall or the slab. So the first column is the one that applies, even for the short bit that is clipped near the board.
Our summers make it count
A west wall or a roof slab in May is already hot before any current flows. The wire starts warm and has less room to heat. That is one more reason never to push a wire to its open-air figure.
Don't crowd one pipe
V-Guard's figures are for the two wires of one circuit. Usual practice: give each circuit its own run of pipe where you can, and don't pull extra circuits through a pipe that is already full. More wires in one pipe means more heat in one place.
Wire limits: V-Guard Classo+ in a pipe. AC and motor lines follow our AC rule: up to 12 A on 2.5 sq mm with 16 A C-curve, 12–16 A on 4 sq mm with 20 A C-curve, above that send us the plate. Long run to a boring or an outhouse: check the drop in the wiring calculator. Price: Ask rate.
Three worked examples
A 1.5-ton AC, a 2 kW geyser and a 1 HP motor
The three lines people ask us about most, worked with the chart. Each has its own detailed page; this is the arithmetic.
1.5-ton split AC
Plate amps decide, not the tonnage
Read the current on the plate. Most 1 and 1.5-ton home splits show 12 A or less.
12 A is well inside 2.5 sq mm (18 A), so the wire is 2.5 sq mm × 3 (phase, neutral, earth).
MCB at or below 18 A: 16 A. C-curve, so the compressor start doesn't trip it.
Plate above 12 A: 4 sq mm and 20 A C-curve. Above 16 A: send us the plate.
The chart only holds if the wire is the size printed on it. Two checks anyone can do with the coil in hand.
Strand count and overall diameter: V-Guard Classo+ table. All four drawn to one scale, about 12 times life size, so they compare truly.
Two checks
Read the print on the insulation: size, brand and the BIS mark run along the whole length. A coil of Classo+ also carries V-Guard's "90 m assured" seal.
Count the strands at a cut end: 1.5 sq mm Classo+ has 30 strands of 0.25 mm, 2.5 sq mm has 48 of 0.25 mm. Fewer strands than that is a thinner wire, whatever the label says.
Thin-for-its-label wire is the usual reason a "2.5 sq mm" line runs hot on a load the chart says is fine. More on spotting it: real or fake wire.
The earth wire is the same size as the phase wire (IS 732), so a 2.5 sq mm line needs three 2.5 sq mm wires. Colours: phase, neutral, earth.
Any size or rating not on the shelf, we order for you; ask on WhatsApp for the time it takes. Today's price for every coil: wire price list · all wire: wires.
Questions people ask us
Short answers
How many amps can 1.5 sq mm wire carry? (1.5 mm taar kitna load leta hai)
V-Guard Classo+ 1.5 sq mm carries 13 A in a pipe in the wall and 16 A clipped in open air. In a house use 13 A, and put a 10 A MCB in front of it. It is the wire for lights and fans.
How many watts can 2.5 sq mm wire carry?
In a wall pipe, 2.5 sq mm Classo+ carries 18 A, about 4,140 W at 230 V. Its MCB is 16 A, so plan the load on that circuit to stay under 16 A, about 3,680 W.
Which MCB for 2.5 sq mm wire?
16 A, never 20 A. The wire carries 18 A in a pipe; a 20 A MCB would let it run between 18 and 20 A without tripping. 20 A goes only on 4 sq mm. C-curve for an AC or a motor, B-curve for sockets and a geyser.
Why is the rating in a pipe lower than clipped?
Heat. In open air the heat leaves the wire; in a pipe buried in plaster it stays, so the wire reaches its safe temperature at a lower current.
Can I use 1.5 sq mm wire for an AC?
No. It carries 13 A in a pipe and takes at most a 10 A MCB, which the AC's start trips. An AC needs 2.5 sq mm with a 16 A C-curve MCB, or 4 sq mm with 20 A if the plate shows more than 12 A. See wire size for an AC.
What about 6 sq mm wire?
V-Guard's Classo+ table stops at 4 sq mm, so we don't print a figure for 6 sq mm here. If a load needs more than 4 sq mm, send us the name plate and the run length; we read the rating off the data sheet of the exact wire we order for you.
Is copper the same as aluminium on this chart?
No. Every figure here is for copper house wire. Aluminium of the same size carries less. See copper vs aluminium wire.
Sashikesh Kumar
Diploma in Electrical, Tashya Ventures
Looks after wires, switchgear, inverters and pumps at our Reva Road store, Muzaffarpur. Every amp figure on this page was checked against V-Guard's own Classo+ table on 13 Nov 2026. Where a rule could go two ways, the page gives the safer one.
Where the numbers come from
V-Guard, Classo+ house wire product page: current for two cables, single phase, in conduit / unenclosed: 0.75 sq mm 6 / 7 A, 1 sq mm 11 / 12 A, 1.5 sq mm 13 / 16 A, 2.5 sq mm 18 / 22 A, 4 sq mm 24 / 29 A; strands 32/0.2, 30/0.25, 48/0.25, 56/0.3; overall diameter 2.5, 2.8, 3.4, 4.0 mm; made to withstand 70 °C; "90 m assured" seal.
IS 732 wiring code (standard figure): earth conductor the same size as the phase conductor up to 16 sq mm.
Standard figures: single-phase supply 230 V; watts ÷ 230 = amps for heaters; 1 HP = 746 W; single-phase 1 HP motor about 8 A running, 2 to 3 times at start.