Pressure pump for a house: when you really need one, and which kind

The short answer

In a house fed from a roof tank, most weak taps are cured by a 1 inch down-line, a clean aerator or a taller tank stand, not a pump. You need a pressure (booster) pump only when the outlet sits too close below the tank: a top-floor shower, a rain shower, an instant geyser, or a bathroom built level with the tank. Then fit a booster on that bathroom's own line, with a bypass and a dry-run cut-off.

0.1
kg/cm² per metreThe only push a tank gives is its height above the tap. Standard figure.
0.18
Top-floor showerTank on the roof of a 2-storey house. Jaquar asks for 0.5 at least.
120 W–1 HP
The range of boostersFrom one shower to a whole house. Bigger is not better.
Push at each tap, 2-storey house
How much pressure each outlet gets from a roof tank A two-storey house with the tank on a low pad on the roof. First-floor shower about 0.18 kg/cm², first-floor basin about 0.30, ground-floor shower about 0.48, ground-floor basin about 0.6. With the tank on a 6 ft stand: 0.37, 0.49, 0.67 and 0.79. Jaquar's minimum for its fittings is 0.5. or on a 6 ft stand FIRST FLOORGROUND FLOORROOF 1.8 m TANK ONROOF6 FTSTAND showerbasinshowerbasin 0.18 0.37 0.30 0.49 0.48 0.67 0.60 0.79 under 0.3: weak 0.3–0.5: taps fine 0.5 and up: shower kg/cm², from height alone
10 ft floors, water in the tank about 0.9 m above the roof, shower 7 ft and basin 3 ft above the floor. 10 m of water height = 1 kg/cm² (standard figure). Pipe losses take a little more away. Jaquar minimum: its data sheet.
Before you spend on a pump

Three checks, and one condition

A pump adds push. It cannot add water and it cannot widen a thin pipe. If one of these is your problem, a pump only makes noise.

1. The pipe leaving the tank

If it is ½ inch, or old GI that has rusted inside, that is your problem. Change to a 1 inch down-line with a ¾ inch branch into each bathroom.

2. The height above the tap

Every metre of tank above the outlet gives 0.1 kg/cm². Measure from the water in the tank down to the shower head. Under 3 m (about 10 ft), a shower will feel weak.

3. The aerator or shower face

Unscrew it. If the flow jumps, boring-water iron grit was choking it. Clean it and you are done. A pump would only push grit in harder.

The condition: a tank that stays full

A booster empties the tank faster than taps do. If your motor can't keep up, or the tank runs dry by evening, sort that first. A booster on an empty tank runs dry and burns out.

The cheaper fix

Raise the tank first, if the outlet only needs a little more

A stand under the tank costs nothing to run, never breaks down and works in a power cut. It is enough for taps and an ordinary shower. It is not enough for a rain shower or an instant geyser on the top floor.

Top-floor outletTank on roof6 ft stand10 ft stand
Basin or kitchen tap3 ft above the floor0.300.490.61
Ordinary shower7 ft above the floor0.180.370.49
Rain shower, body jets, instant geyserneed more push than gravity givesBooster. Read the minimum pressure in the product's manual.
Bathroom on the roof, beside the tankwater barely above the outletBooster. A stand can't climb high enough.

kg/cm², height alone, same house as the drawing above. Standard figure: 1 m of height = 0.1 kg/cm².

Before you build a stand A full 1,000 litre tank weighs about a tonne (a litre of water is 1 kg). The stand must sit over a beam or column, not the middle of the slab, and that is your engineer's call. Brick columns or an RCC platform, with the washout and overflow led to a drain and a fixed ladder for cleaning. More on this: tank platform on the roof · overhead tank setup.

Send a photo of your roof and tank on WhatsApp. If a stand will do, we will say so and send the cement, sariya and pipe list instead of a pump.

What "pressure pump" can mean

Four kinds of booster, and the house each one suits

All four start by themselves when a tap opens. They differ in how much they push, how many taps they feed at once, and what happens between uses. Figures are the makers' own, for one example model of each kind.

from tank, ½ inch flow switch inside

AInline mini booster

One shower, or the pipe into a geyser
  • Grundfos UPA 15-90: 120 W, at most 9 m (0.88 bar) extra, 16 L/min at 5.46 m.
  • Starts by itself above 90–120 L/h of flow. ½ inch unions. Takes hot water too.
  • Catch: it needs at least 0.2 bar (2 m of water) at its own inlet. A tank level with the pump won't feed it.
float cuts it off 0.5 or 1 HP

BBooster pump, 0.5–1 HP

One bathroom, or one floor
  • Crompton Mini Force II: 0.5 HP (0.37 kW), 7–34 L/min.
  • Crompton Mini Force I: 1 HP, up to 42 m, 960–3000 L/h.
  • Both: float switch for dry-run, 180–260 V. Starts and stops with the tap.
pressure switch tank

CPump with pressure tank

The whole house, 2–4 bathrooms
  • Crompton CFMSMB 0.5 HP (V24): up to 45 m, 21–60 L/min, float switch.
  • The tank holds some water under pressure, so the pump does not start for every glass.
  • Pressure rises and falls between the switch's on and off points: you feel it in the shower.
2.5 steady pressure, speed changes

DConstant-pressure pump

Rain showers, 3+ bathrooms, quiet
  • Grundfos SCALA2: up to 45 m, 3 m³/h at 27 m, 10 bar body.
  • Speeds up and slows down to hold one pressure. Grundfos India gives 44 dB(A).
  • Costs the most. Worth it where the pump sits near a bedroom.
What you care aboutA · inlineB · boosterC · with tankD · constant
Taps it can feed at onceoneone bathroomseveralseveral
Push addedunder 1 barplentyplentyplenty, steady
Starts and stopswith the tapwith the tapby pressure; tank cushions itsmoothly
Needs height at its inletyes, 2 msee the maker's manualsee the maker's manualsee the maker's manual
PriceAsk rateAsk rateAsk rateAsk rate

HP is not the answer. None of these makers prints a bathroom count. Read the flow (litres a minute or an hour) and the head (metres) on the sheet. Our Nova 0.5 HP and 1 HP pumps fill the tank from the boring. They are not boosters and have no switch to stop when the tap shuts.

Which one for your house

Answer three questions

This gives the kind and size we would suggest, and the parts that go with it. It follows usual practice; the final check is the maker's flow figure against your outlets.

The pump goes on the line from the tank, never on the street supply or the boring. If the pump will sit a floor below the tank, choose "on a stand".

What we would fit

—
—
    Pump and partsAsk rate
    Send this to Sashikesh on WhatsApp

    We can order the booster for you; ask on WhatsApp for the time it takes. Send a photo of the tank and the weak tap with it.

    Fitting it right

    Where the booster goes, and the parts around it

    Most booster trouble is in the fitting, not the pump. This is the layout for one boosted bathroom; the rest of the house stays on gravity.

    How a booster pump is fitted after the roof tank Tank with a float switch. Its outlet has a ball valve. A tee sends one line to the rest of the house by gravity and one to the booster. On the booster line: ball valve, union, the pump, a non-return valve, union, ball valve, then down to the bathroom. A bypass pipe with its own non-return valve runs round the pump. The pump has its own MCB, wire and earth. PUMP rest of the house,gravity as before boosted bathroom ROOF 1 2 3 4 5 6 7
    Drawn for a booster on the roof below the tank's outlet, so water flows into it by itself. Brass = unions. Triangles = non-return valves, pointing the way water flows.
    1. Dry-run cut-off in the tankA float switch (types B and C from Crompton have one) or a separate one. It stops the pump before the tank runs dry. We can order a float switch for you.
    2. Ball valve at the tank, and a teeThe tee gives the booster its own line. The house keeps its gravity line. Ball valve · tee
    3. Ball valve and union before the pumpSo the pump can come off for repair without draining the tank. Union · MTA/FTA adaptors to go from pipe to the pump's thread.
    4. The pump, on a firm base, under a coverShaded from sun and rain, bolted down, not hanging on the pipe. Match the pipe to the pump's ports: 1 inch on most 0.5–1 HP boosters (Crompton lists 25×25 mm), ½ inch unions on the inline type. 1 inch UPVC
    5. Non-return valve after the pump, then union and ball valveStops water running back through the pump when it stops. We can order a non-return valve for you.
    6. Bypass with its own non-return valveA pipe around the pump. In a power cut, or while the pump is out for repair, water still flows by gravity. This one part matters most in Muzaffarpur.
    7. Its own switch, MCB and earthFor a pump up to 1 HP, 2.5 sq mm wire and a 16 A C-curve MCB, with the earth wire the same size as the phase. The plug-in inline type needs an earthed socket. 2.5 sq mm wire · MCB · wire for a motor

    Old pipes: UPVC itself is rated far above any house booster (Prince lists 42.4 kg/cm² for 15 mm Sch-40), but its threaded joints are rated at half the pipe, and old GI joints often weep once pressure rises. Check the boosted line for drips in the first week.

    What goes wrong

    Four mistakes we see after a booster is fitted

    TAP SHUT, STILL RUNNING

    An ordinary motor in the tap line

    You see: hot pump, burst joint

    A water motor has no switch that knows when a tap shuts. It keeps pushing against closed taps. A booster has a flow or pressure switch for exactly this.

    POWER CUT: NOTHING

    No bypass

    You see: a dry shower in every power cut

    The pump blocks the pipe when it stops. A bypass with a non-return valve lets gravity water through. It costs a few fittings.

    DRY RUN: SEAL BURNS

    No dry-run cut-off

    You see: a pump that whines, then leaks

    The tank runs low, the pump sucks air and its seal and winding heat up. A float switch in the tank stops it in time.

    street supply, shared

    Pump on the street supply

    You see: neighbours short of water, dirty water

    It pulls water from the shared pipe, and when the supply stops it can suck dirt in through leaky joints. Let the supply fill a tank or sump, then boost from that.

    For this job

    The booster, and what goes around it

    Non-return valves, float switches and any size not listed we can order for you; ask on WhatsApp for the time it takes. Today's prices: pipe rates.

    Read next

    Questions people ask us

    Short answers

    Which pressure pump is best for a home?

    The one that matches what is weak. For one shower or a geyser, a small inline booster with a flow switch. For one bathroom or one floor, a 0.5 HP booster with a dry-run float. For the whole house, a booster with a pressure tank, or a constant-pressure pump if you want a steady rain shower and less noise. Brand matters less than fitting it with a bypass and a dry-run cut-off.

    How many HP for 2 bathrooms?

    Usual practice: 0.5 HP if only one bathroom runs at a time, 1 HP if both showers run together. Go by the maker's flow figure, not the HP: Crompton's 0.5 HP Mini Force II gives 7–34 litres a minute, its 1 HP Mini Force I 960–3000 litres an hour.

    Can I use my ordinary motor as a pressure pump? (motor se pressure badhega?)

    No. An ordinary self-priming motor such as our Nova 0.5 HP fills the tank. It has no pressure or flow switch, so in a tap line it keeps running when every tap is shut, heats up and strains the joints. A booster starts when a tap opens and stops when it closes.

    Will it work in a power cut?

    The pump stops. With a bypass pipe and a non-return valve around it, water still comes from the tank by gravity, at the old weaker pressure. Without a bypass, the boosted bathroom gets little or nothing until power returns.

    How much electricity does it use?

    It runs only while a tap is open. A 0.5 HP booster draws about 0.37 kW, so an hour of use a day is about 11 units a month. A 120 W inline booster used an hour a day is under 4 units a month.

    Can the small inline booster go on the roof beside the tank?

    Only if the water in the tank stands at least 2 m above it. Grundfos asks for 0.2 bar at the UPA 15-90's inlet to avoid cavitation noise and bearing damage. Beside a tank on the same roof it doesn't get that. Fit it a floor lower, or choose a booster of type B.

    Can a booster go on the street supply line?

    We don't advise it. A pump on a shared pipe pulls water away from the neighbours, and when the supply stops it can suck dirty water in through leaky joints. Let the supply fill a tank or sump, and boost from that.

    Will higher pressure burst my pipes?

    Not UPVC or CPVC pipe in good condition: Prince rates 15 mm Sch-40 UPVC at 42.4 kg/cm², far above a house booster. Weak points are threaded joints (rated at half the pipe), old GI joints and cheap flexible connectors. Watch the boosted line for drips in the first week.

    Sashikesh Kumar
    Diploma in Electrical, Tashya Ventures

    Looks after wiring, MCBs, fans, inverters and pumps at our Reva Road store, Muzaffarpur. The pump figures on this page were checked against Crompton's product pages and Grundfos's data booklet on 13 Nov 2026. Height figures are standard physics; bathroom-to-pump matching is usual practice and labelled so.

    Where the numbers come from

    1. Standard figure (hydrostatics): 10 m of water = 1 kg/cm² ≈ 0.98 bar; a litre of water weighs 1 kg.
    2. Jaquar, data sheet for ALD-CHR-069FT concealed stop cock body: recommended pressure 0.5–5 bar.
    3. Grundfos, UPA Home Booster data booklet: UPA 15-90 integrated flow switch, starts above 90–120 L/h, minimum 2.0 m / 0.2 bar at the suction port, horizontal shaft, Rp ¾–Rp ½ unions, max 6 bar.
    4. Grundfos UPA 15-90 N (99539153), product data: 120 W, max head 9 m (0.88 bar), 16 L/min at 5.46 m, 2–95 °C, no pressure vessel needed.
    5. Crompton, Mini Force II: 0.5 HP, 0.37 kW, 7–34 L/min, float switch, 180–260 V.
    6. Crompton, Mini Force I: 1 HP, max head 42 m, 960–3000 L/h, float switch, 180–260 V.
    7. Crompton, CFMSMB3D0.50-V24: 0.5 HP, max head 45 m, 21–60 L/min, float switch; CFMSMB series page: pressure switch.
    8. Grundfos India, SCALA2 for modern homes: 44 dB(A). SCALA2 3-45 data sheets: max head 45 m, rated 3 m³/h at 27 m, 10 bar maximum operating pressure.
    9. Prince Pipes, EasyFit UPVC pressure table: 15 mm Sch-40 = 42.40 kg/cm² at 23 °C; threaded joints 50% of rating.
    10. Wire and MCB rule: V-Guard Classo+ table (2.5 sq mm in a wall pipe carries 18 A, so a 16 A MCB); earth same size as phase (IS 732).
    11. Which booster for how many bathrooms, the fitting layout and the street-supply advice: usual practice, labelled on the page.