1000 sq ft chhat mein kitna sariya lagega?
In our worked example, a 40 × 25 ft roof with 10 mm bars at 6 inches both ways, top bars over the beams and 10% for laps and cut ends: about 1,314 kg. With 12 mm main bars, about 1,403 kg. Your drawing's sizes and spacing change it; the calculator above takes them.
Is 4 kg per sq ft right for a slab?
No. 3.5 to 5 kg per sq ft of built-up area is the figure for a whole RCC house, footings to roof. The roof slab alone came to about 1.3 to 1.4 kg per sq ft in our example, top layer included.
Lenter mein kitne mm ka sariya lagta hai?
House slabs are usually drawn in 10 mm and 12 mm, sometimes with 8 mm distribution bars. IS 456 limits the bar size to one-eighth of the slab thickness, so 15 mm for a 125 mm slab. Your drawing names the size. Size by size for the whole house: which mm sariya where.
6 inch or 8 inch spacing?
Whatever the drawing says. The code's outer limits are 300 mm for main bars and 450 mm for distribution bars in a normal house slab, and house drawings usually sit well inside them. Every inch more between bars is less steel in the slab, so never open it up on site.
How many 12 m bars, and how many bundles?
Divide total metres by 12 and round up. Version A is 178 bars of 10 mm; version B is 58 of 12 mm and 107 of 10 mm. Bars per bundle differ by size and maker, so we bill by weighed kg. Our counts: bars in a bundle.
How much binding wire for the slab?
Usual practice is 8 to 12 kg per tonne of sariya, so about 11 to 17 kg for a 1000 sq ft slab like ours. Close spacing means more crossings and more wire. More in how much binding wire.
Why are extra bars needed on top over the beams?
Over a beam or wall the slab bends the other way, so the top face pulls apart. Bars near the top, held up on chairs, take that pull. Leave them out, or let them get trodden flat, and cracks open along the beam lines on the roof.