Asli ya nakli taar? Seven checks on a wire coil before you pay
Sashikesh Kumar, Diploma in Electrical · checked against IS 694 and the makers' own tables, 13 Nov 2026
The short answer
Print on the wire itselfMaker's name at least every metre, with size and type. It must not rub off with a wet cloth.
A full label on the coilIS number, size, FR or FR-LSH, length, approximate gross mass, year.
A licence number that checks outThe CM/L number in the free BIS Care app shows the same maker.
The maker's own checkV-Guard's QR on the box; Ultravolt's wire authenticity checker.
Strands at a cut end1.5 sq mm Classo+: 30 strands. 2.5 sq mm: 48. Fewer is thinner wire.
Weight of the coilClose to the gross mass on the label, and never under the copper alone.
Resistance, end to endA whole 90 m coil of 1.5 sq mm reads at most about 1.2 Ω.
Checks 1 to 4 catch a false brand. Checks 5 to 7 catch what does more harm: a real-looking coil that is thinner or shorter than its label. Then keep the GST bill.
1 m
Most gap between printsIS 694 makes the maker's name repeat at least every metre on the insulation.
30 / 48
Strands in Classo+1.5 sq mm and 2.5 sq mm, each strand 0.25 mm (V-Guard table).
1.2 Ω
Whole 90 m coil, 1.5 sq mmFrom the 13.3 Ω per km limit, at 20 °C. Thin wire reads higher.
What a genuine coil tells you
Drawn to show what to look for, not any maker's artwork. Label items and the 1 m rule: IS 694:2010, clauses 11 and 15.2. Durability: rub lightly ten times with wet cotton or cloth (clause 11.1).
What "nakli" really means
Three ways a buyer ends up with bad wire
Only the first one is a fake brand. The other two can come in a box that looks right, and they are the ones that heat up inside a wall.
1A false brand
Cheap wire packed in boxes printed with a known name. In July 2024 Hyderabad police seized duplicate wire worth about ₹77 lakh from one godown, packed in branded companies' boxes for sale in the market.
Caught by: checks 1, 2, 3, 4
2Less copper than the label
Sold as 2.5 sq mm, made with fewer or thinner strands, sometimes with thicker plastic so it looks the same size from outside. Or aluminium strands with a thin copper skin. It works on day one. It runs hot on a full load.
Caught by: checks 5, 6, 7
3A short coil
The label says 90 m, the coil holds less. You find out when the electrician asks for one more coil halfway through a floor. Short and thin together is the worst: the coil feels "normal" in the hand.
Caught by: checks 2, 6, 7
Why the thin wire matters most: the MCB is picked from the wire's size. A "2.5 sq mm" line gets a 16 A MCB because real 2.5 sq mm carries 18 A in a wall pipe. If the copper is really 1.5 sq mm (13 A), the MCB lets it overheat for hours without tripping. The full sizes and MCBs: wire amps chart.
At the counter, in this order
The seven checks, and what each one catches
The first four take two minutes with the coil in your hand and a phone. The last three need a cut end, a scale or a multimeter. Ask us and we will do them with you before you pay.
1
On the insulation
Read the print along the wire
IS 694 says the maker must be named throughout the length of the wire, printed, indented or embossed, with no more than 1 m between two prints.
Brand name, size in sq mm, voltage grade and type (FR, FR-LSH, HR FR, HFFR) repeat along the wire.
Rub the print ten times with a wet cloth. IS 694 uses this exact test: the name must stay.
Unroll a few turns. Print at the outside end only, or a gap of several metres, is a stop.
Stop if the size is not printed on the wire. Without it, nobody can prove later what went into your wall.
2
On the coil label
Read the label, item by item
IS 694 (clause 15.2) lists what the label must carry. A genuine label has all of it; a hurried fake usually skips some.
IS 694 (IS 17048 for halogen-free wire such as Ultravolt NextGen)
Maker's name, type and voltage grade, FR or FR-LSH
Size, colour and length (90 m, or 180 m on some ranges)
Approximate gross mass: you will use it in check 6
Country and year of manufacture
Stop if the label's size or length differs from what is printed on the wire.
3
Phone · BIS Care app
Check the licence number
A forger can print the ISI logo. He cannot make BIS's own records show his number for V-Guard or UltraTech. Type the number after CM/L into the free BIS Care app, under licence details.
It must show the same company as the brand, the product as cable, and IS 694 (or IS 17048).
Ultravolt prints its numbers on its data sheets: CM/L 7100158506 for SafePlus and GreenCore, CM/L 7100158405 for NextGen.
Classo+: V-Guard's page says "made in accordance with BIS requirements" but prints no number, so read it on the coil.
The app steps, with pictures, are on our cement check page; they are the same for wire.
4
Phone · maker's page
Use the maker's own check
V-Guard: scan the QR code on the box at V-Guard's product-genuine page. A genuine product says so and offers "Register Product"; a failed one says it is not genuine and asks you to contact the dealer or customer care.
Ultravolt: its website lists a Wire Authenticity Checker. We rely on the BIS Care check above, which works the same for every brand.
Not enough alone. A QR sticker can be copied onto a fake box. That is why Havells built copy-proof labels for its cables. Do check 4 with checks 1 to 3, not instead of them.
5
At a cut end · 2 cm
Count the strands, look at the copper
Strip 2 cm and count. Classo+ 1 sq mm: 32, 1.5: 30, 2.5: 48, 4: 56 (V-Guard table). Ultravolt SafePlus 1.5: 22 thicker strands; GreenCore and NextGen 1.5: 30.
The copper should be bright and the same colour right through. Scrape one strand with a blade: silver-grey under a copper skin is aluminium.
Bend the end back and forth: the plastic should not crack or turn white.
6
On a scale
Weigh the coil
Copper is heavy. A coil with less copper, or fewer metres, is lighter, and the label has already told you what it should weigh.
Weigh it on a shop scale and compare with the approximate gross mass on the label (check 2).
The coil can never weigh less than its copper alone: about 1.2 kg for 90 m of 1.5 sq mm, 1.9 kg for 2.5 sq mm, 3.2 kg for 4 sq mm. The plastic comes on top.
Ask if it is clearly lighter than the label says. Two coils of the same size and brand side by side should weigh nearly the same.
7
Multimeter · electrician
Read the resistance, end to end
Thin copper or aluminium shows up as higher resistance. Touch the two bare ends of the coil to the meter, after first touching the probes together and taking that small reading off.
Whole 90 m coil, at most: 1 sq mm 1.76 Ω, 1.5 sq mm 1.20 Ω, 2.5 sq mm 0.72 Ω, 4 sq mm 0.45 Ω (at 20 °C).
On a hot day allow about 6% more. A 1.5 sq mm coil reading near 1.8 Ω is 1 sq mm copper.
Checks 6 and 7 together also catch a short coil: a short coil reads low on the meter and light on the scale; a thin coil reads high on the meter. If you want to see the metres for yourself, read the metre count printed at both ends where the wire has one; a Classo+ coil also carries V-Guard's "90 m ASSURED" seal.
Numbers for your coil
What a genuine 90 m coil should show, size by size
Strands, outside size and plastic thickness from V-Guard's Classo+ table. Resistance from the same table, which matches the IS limit for flexible copper wire. Copper weight is our arithmetic.
Size
Strands × thickness
Outside, plastic
Most resistance, 1 km
Whole 90 m coil, at most
Copper alone in 90 m
Used for
1 sq mm
32 × 0.20 mm
2.5 mm · 0.6 mm
19.5 Ω
1.76 Ω
about 0.8 kg
Switchboard to light and fan points
1.5 sq mm
30 × 0.25 mmSafePlus: 22 × 0.30 mm
2.8 mm · 0.6 mm
13.3 ΩSafePlus: 12.1 Ω
1.20 Ω
about 1.2 kg
Light and fan circuits
2.5 sq mm
48 × 0.25 mm
3.4 mm · 0.7 mm
7.98 Ω
0.72 Ω
about 1.9 kg
16 A sockets, geyser, AC up to 12 A
4 sq mm
56 × 0.30 mm
4.0 mm · 0.8 mm
4.95 Ω
0.45 Ω
about 3.2 kg
AC of 12–16 A, sub-board feed
Coil resistance = the per-km figure × 0.09. Copper = strand area × 90 m × 8.89 g per cubic cm. The whole coil weighs more, because of the plastic; the label's gross mass is the figure to match. For Ultravolt sizes other than 1.5 sq mm, count against the range's data sheet. Which size goes on which circuit: wire amps chart.
Check your coil
Put in what you counted, weighed or measured
Fill in only what you have. Each line is judged on its own.
Your coil
Strands—Count the strands at a 2 cm cut end.
Resistance—Limit for this size and length appears here.
Weight—Copper alone and the label figure appear here.
Limits: IS figures for flexible copper wire, as in V-Guard's Classo+ table, with 6% allowed for a hot day. A pass here does not replace checks 1 to 4. Coil prices for every size: wire price list.
Where you buy
The bill is the check that lasts
Once wire is inside a wall, the print you can still read and the GST bill are the only proof of what you paid for.
What comes with every coil from us
A full 90 m coil with its label and seal, so what the label says is what you take home.
A GST bill naming the brand, range, size and colour.
Our V-Guard Classo+ comes to us on Grasim / Birla Pivot purchase bills. UltraTech Ultravolt we order for you; it comes on the same GST bill as your cement.
Ask, and we will open a coil, count the strands and weigh it in front of you.
Other brands
We sell genuine Polycab, Havells and Finolex wire with a GST bill; we can order any of them for you, ask on WhatsApp for the time it takes. The seven checks work for every brand. Several makers add their own: Havells has a Checko app that scans a copy-proof label on its flexible cables, and Finolex says its packs carry QR codes to scan. Brands side by side: wire brands compared.
Wire already in your wall?
With the main switch off, have your electrician open one switchboard, and send us a clear photo of the print on the wire behind it on WhatsApp. We will tell you the brand, size and type it says, and whether that suits the load you want to add. What the letters mean: FR, FRLS, HFFR wire.
Any size, colour or range not on the shelf we can order for you; ask on WhatsApp for the time it takes. Classo+ against Ultravolt, point by point: Classo+ vs Ultravolt. How many coils a house needs: wire coils for a house. Today's price for every coil: wire price list.
Questions people ask us
Short answers
How do I identify original wire? (asli taar ki pehchan)
Read the print on the insulation: IS 694 makes the maker print its name at least once every metre, and good print does not rub off with a wet cloth. Check the coil label carries the IS number, size, type, length and approximate gross mass. Type the CM/L licence number into the BIS Care app. Then count the strands at a cut end against the maker's table, and weigh the coil.
Is the ISI mark on the box enough?
No. A box can be printed anywhere. The maker's name must be printed on the wire itself, and the licence number on the label must check out in the BIS Care app under the same company and IS 694 (or IS 17048 for halogen-free wire).
Does the lighter test show if a wire is FR?
Not reliably. FR is proved in a laboratory by an oxygen index test, which IS 694 sets at not less than 29%. A lighter flame in a shop tells you little and is a fire risk. Check the FR or FR-LSH wording on the wire and label, and the licence, instead.
Does a deeper copper colour mean better wire?
No. Colour cannot show purity. What matters is that the copper is bright and the same right through, with no silver core under a scraped strand, and that the strand count, weight and resistance match the size. Tinned copper wire is silver on purpose; its label must say ATC, and it is not what house wiring uses.
Why is fake wire dangerous if the bulb still lights?
Because the usual fake is thinner than its label. A wire sold as 2.5 sq mm but made like 1.5 sq mm sits behind a 16 A MCB chosen for real 2.5 sq mm. The MCB lets through more current than the thin copper can carry, so the wire heats inside the wall without tripping.
Can I buy wire by the metre from you?
We sell full 90 m coils. A whole coil keeps its label, seal and print, which is your proof of what went in. For a short job, ask on WhatsApp what is possible on the day.
Is UltraBolt the same as Ultravolt?
Yes. UltraTech's wire is spelt Ultravolt; most people say UltraBolt. Its SafePlus and GreenCore ranges carry BIS licence CM/L 7100158506 and NextGen carries CM/L 7100158405, as printed on Ultravolt's data sheets.
A coil is much cheaper than everywhere else. Is it fake?
Not always, but copper sets most of a coil's price. A coil far below every other price for the same size, length and type usually has less copper or fewer metres. Run checks 5 to 7 before you buy it. How the coil price is made up: wire price list.
Sashikesh Kumar
Diploma in Electrical, Tashya Ventures
Looks after wires, switchgear, inverters and pumps at our Reva Road store, Muzaffarpur. Every figure on this page was checked on 13 Nov 2026 against IS 694:2010, V-Guard's Classo+ table and Ultravolt's data sheets. Where a check can be read two ways, the page gives the stricter one.
Where the numbers come from
Bureau of Indian Standards, IS 694:2010, PVC insulated cables up to 1100 V: clause 11 (maker's name printed, indented or embossed throughout the length, at most 1 m apart), 11.1 (durability: rub lightly ten times with wet cotton or cloth), 15.2 (label items, including length and approximate gross mass), 10.5 (oxygen index not less than 29%).
V-Guard, Classo+ triple layer insulation wire: strands 24/0.2, 32/0.2, 30/0.25, 48/0.25, 56/0.3; most resistance 26, 19.5, 13.3, 7.98, 4.95 Ω/km at 20 °C; overall 2.3–4.0 mm; insulation 0.6–0.8 mm; "90 m ASSURED"; "manufactured in accordance with BIS requirements".
Ultravolt, SafePlus data sheet (1.5 sq mm 22 × 0.30 mm, 12.1 Ω/km, IS 694, CM/L 7100158506), GreenCore and NextGen (IS 17048, CM/L 7100158405); home page listing the Wire Authenticity Checker.
Our arithmetic: coil resistance = Ω/km × 0.09; copper weight = strands × strand area × 90 m × 8.89 g/cm³; copper resistance rises about 0.4% per °C, so about 6% from 20 °C to 35 °C.
Not sure about a coil?
Send a photo of the print on the wire and the label. We'll tell you what to check, or bring it to the store and we'll check it with you.