Buying a total, not colours
Five coils of one colour don't wire anything. Each size is bought as red, black and green, about a third each.
Each room count includes a kitchen and a bathroom. Wire is bought in sets of three coils: red for phase, black for neutral, green for earth, all the same size. So one "set" of 1.5 sq mm is 270 m of wire but only about 90 m of circuit. Up to two rooms, one set of each size usually covers it. Add the main from the meter: about 33 m of 4 or 6 sq mm.
Every row is worked with the same point list and lengths shown further down. "Room" means a bedroom or hall: two lights, a fan and two 6 A sockets, plus one 16 A socket.
| House | 1.5 sq mm | 2.5 sq mm | Main wire | Pipe, 3 m lengths | MCBs |
|---|---|---|---|---|---|
| 1 room, kitchen, bathno AC, no geyser | 3 coils1 of each colour · ~211 m used | 3 coils1 of each colour · ~83 m used | 4 sq mm, ~33 m | 22 × 20 mm 13 × 25 mm | B10 ×2, C16 ×2+ DP main, RCCB |
| 2 rooms, kitchen, bath1 AC, 1 geyser, water pump | 3 coils~281 m used | 3 coils~218 m used | 6 sq mm, ~33 m | 30 × 20 mm 28 × 25 mm | B10 ×2, C16 ×4, 16 A DP ×1+ DP main, RCCB |
| 3 rooms, kitchen, 2 baths1 AC, 1 geyser, water pump | 6 coils2 of each colour · ~380 m used | 3 coils~238 m used | 6 sq mm, ~33 m | 41 × 20 mm 31 × 25 mm | B10 ×2, C16 ×4, 16 A DP ×1+ DP main, RCCB |
| Two floors, 2 rooms each1 kitchen, bath, AC and geyser on each floor, pump | 6 coils~535 m used | 6 coils~375 m used | 6 sq mm, ~33 m | 55 × 20 mm 46 × 25 mm | B10 ×4, C16 ×6, 16 A DP ×2+ DP main, RCCB |
| Three floors, 2 rooms eachkitchen, bath, AC and geyser on every floor, pump | 12 coils4 of each colour · ~911 m used | 9 coils3 of each colour · ~693 m used | 6 sq mm, ~33 m | 92 × 20 mm 81 × 25 mm | B10 ×6, C16 ×10, 16 A DP ×3+ DP main, RCCB |
Why 1 room and 2 rooms come out the same. A one-room house still needs red, black and green in both sizes, and one coil of each is the smallest you can buy. The 2.5 sq mm left over in a one-room house is not wasted: it is the line for the AC or geyser you add later.
Which size goes where follows the wire amps chart: 1.5 sq mm (13 A in a pipe, 10 A MCB) for lights, fans and 6 A sockets; 2.5 sq mm (18 A, 16 A MCB) for 16 A sockets, the kitchen, the geyser (16 A double-pole MCB, as CPWD's wiring specification recommends for water heaters) and an AC up to 12 A; 4 sq mm (24 A, 20 A MCB) only for an AC of 12–16 A. Which MCB on which line: which MCB for which load.
Every run of pipe carries three wires of the same size. So the metres of wire are three times the metres of pipe, and the coils have to be bought in three colours.
"Four coils of 1.5" means nothing to an electrician until he knows which colours. Each colour has to cover its third of the run. That is why the counter below gives every size as red, black and green.
Every socket and every metal fitting gets an earth wire, the same size as its phase: 2.5 sq mm earth on a 2.5 sq mm line. We count earth to every point. Leaving it out saves a coil and leaves the house without protection. More in earthing basics.
The counter adds 10% spare. If one colour comes out up to 8 m over a whole coil, it doesn't add a coil: those metres come out of the spare. More than that, it adds one.
Which colour does which job, and why yellow or blue can also carry phase: phase, neutral and earth colours.
No maker publishes metres per room, so these are usual practice in Muzaffarpur houses: pipe in the slab and the walls, one distribution board (DB) on the ground floor near the meter. Each length is pipe; wire is three times it.
Take one floor plan: 2 rooms, a bathroom, an AC and a geyser. Every circuit on it starts at the DB downstairs, so each floor up adds a climb to every run.
Building one floor now and one later? Lay the pipe for the upper floor's runs while the ground floor is being done, and pull its wire when you build. Pipe in a slab goes in before the casting: conduit before slab casting · fan box before casting.
Put in each floor as it will be finished. Leave a floor at zero if you are not building it. The lengths behind it are the ones listed above.
Typical figures from usual-practice lengths, with 10% spare; your electrician's point list decides. Coils: Classo+ 90 m. Switches, sockets, plates and the DB box are on the whole-house wiring kit; run lengths and voltage drop in the wiring calculator. Price: Ask rate.
Five coils of one colour don't wire anything. Each size is bought as red, black and green, about a third each.
Earth is the same size as the phase beside it (IS 732). A 2.5 sq mm socket line has a 2.5 sq mm green.
Fridge, mixer and microwave go on 16 A sockets and 2.5 sq mm. 1.5 is for lights, fans and 6 A sockets only.
Check the length seal and the size printed along the wire before the coil is opened. Classo+ carries a "90 m assured" seal. More: real or fake wire.
Prices are from our latest bill and change often. Please confirm today's rate on WhatsApp or call before buying.
Classo+ 1.5 sq mmLights, fans, 6 A sockets · 13 A in a pipe₹ 1,992per 90 m Classo+ 2.5 sq mm16 A sockets, kitchen, geyser, AC · 18 A₹ 3,211per 90 m Classo+ 4 sq mmAC of 12–16 A, the main up to 4.6 kW · 24 AAsk today's rateper 90 m 6 sq mm main wireMeter to DB · we order it for youAsk today's rateyour length UltraTech UltraBolt wireThe other range we sellAsk today's rateper coilAny size, colour or rating not on the shelf, we order for you; ask on WhatsApp for the time it takes. Today's coil prices: wire price list. The order the work goes in, slab to switch plate: new house wiring checklist.
Typically six 90 m coils: one red, one black and one green of 1.5 sq mm, and the same of 2.5 sq mm, for 2 rooms, a kitchen and a bathroom with one AC, a geyser and a pump. Plus about 33 m of 6 sq mm main from the meter.
Square feet alone don't decide it; rooms, points and floors do. A 1,000 sq ft single floor with 3 rooms, a kitchen and 2 baths comes to about 380 m of 1.5 sq mm and 240 m of 2.5 sq mm on our count: 9 coils. Online rules of thumb run from about 300 m to over 800 m for the same area, which is why we count points instead.
Every run carries a phase (red), a neutral (black) and an earth (green) of the same size. Each colour covers its own third, so the smallest you can buy for one size is one coil of each colour.
Not in house wiring: IS 732 takes the earth wire the same size as the phase up to 16 sq mm. 2.5 sq mm line, 2.5 sq mm green.
1 sq mm (11 A in a pipe) can feed a light or fan point from its board. We count 1.5 sq mm (13 A) for the whole light circuit: one size, fewer coils of different sizes, and room for more points later. See the wire amps chart.
Pipe and boxes go in first, at the slab and before plaster; wire is pulled after plaster. Buy the pipe at the slab stage and the wire when the walls are plastered, from the same list.
It should be. Classo+ coils carry V-Guard's "90 m assured" seal, and the size and BIS mark are printed along the wire. Check both before the coil is opened.
Looks after wires, switchgear, inverters and pumps at our Reva Road store, Muzaffarpur. The lengths on this page are usual practice for houses here, counted point by point; the wire sizes follow V-Guard's own Classo+ table, as on our wire amps chart.
Rooms, ACs and floors, or a photo of the electrician's point list. We'll send back coils by size and colour, pipe, boxes and MCBs, with today's price, on WhatsApp.