Wiring guide · how much to buy

How many 90 m wire coils does a house need? Size by size, for 1, 2 and 3 rooms and each floor

The short answer · single floor, typical points
1 room
6coils of 90 m
3 + 31.5 + 2.5 sq mm
2 rooms
6coils of 90 m
3 + 31.5 + 2.5 sq mm
3 rooms
9coils of 90 m
6 + 31.5 + 2.5 sq mm

Each room count includes a kitchen and a bathroom. Wire is bought in sets of three coils: red for phase, black for neutral, green for earth, all the same size. So one "set" of 1.5 sq mm is 270 m of wire but only about 90 m of circuit. Up to two rooms, one set of each size usually covers it. Add the main from the meter: about 33 m of 4 or 6 sq mm.

Typical figures, not a rule. Your electrician's point list decides. Put your own rooms, ACs and floors in the counter below; it does the same arithmetic.
Coils for a single-floor house
Wire coils needed for a 1, 2 and 3 room house Three columns. 1 room: one red, one black and one green coil of 1.5 sq mm, and the same of 2.5 sq mm, 6 coils. 2 rooms: the same 6 coils. 3 rooms: two of each colour in 1.5 sq mm and one of each in 2.5 sq mm, 9 coils. Plus about 33 m of main wire. 1 room2 rooms3 rooms kitchen, bath+ AC, geyser, pump2 baths, AC, geyser 1.5 sq mm · lights, fans, 6 A sockets 2.5 sq mm · 16 A sockets, kitchen, AC, geyser 6 coils6 coils9 coils uses about 294 muses about 499 muses about 618 m phase neutral earth, same size Plus the main from the meter: about 33 m of 4 or 6 sq mm.
Our counter's figures for the house types in the table below, with 10% spare for bends and board tails. Coils: V-Guard Classo+, 90 m each.
House by house

Coils, pipe and MCBs for five common houses

Every row is worked with the same point list and lengths shown further down. "Room" means a bedroom or hall: two lights, a fan and two 6 A sockets, plus one 16 A socket.

House1.5 sq mm2.5 sq mmMain wirePipe, 3 m lengthsMCBs
1 room, kitchen, bathno AC, no geyser3 coils1 of each colour · ~211 m used3 coils1 of each colour · ~83 m used4 sq mm, ~33 m22 × 20 mm
13 × 25 mm
B10 ×2, C16 ×2+ DP main, RCCB
2 rooms, kitchen, bath1 AC, 1 geyser, water pump3 coils~281 m used3 coils~218 m used6 sq mm, ~33 m30 × 20 mm
28 × 25 mm
B10 ×2, C16 ×4, 16 A DP ×1+ DP main, RCCB
3 rooms, kitchen, 2 baths1 AC, 1 geyser, water pump6 coils2 of each colour · ~380 m used3 coils~238 m used6 sq mm, ~33 m41 × 20 mm
31 × 25 mm
B10 ×2, C16 ×4, 16 A DP ×1+ DP main, RCCB
Two floors, 2 rooms each1 kitchen, bath, AC and geyser on each floor, pump6 coils~535 m used6 coils~375 m used6 sq mm, ~33 m55 × 20 mm
46 × 25 mm
B10 ×4, C16 ×6, 16 A DP ×2+ DP main, RCCB
Three floors, 2 rooms eachkitchen, bath, AC and geyser on every floor, pump12 coils4 of each colour · ~911 m used9 coils3 of each colour · ~693 m used6 sq mm, ~33 m92 × 20 mm
81 × 25 mm
B10 ×6, C16 ×10, 16 A DP ×3+ DP main, RCCB

Why 1 room and 2 rooms come out the same. A one-room house still needs red, black and green in both sizes, and one coil of each is the smallest you can buy. The 2.5 sq mm left over in a one-room house is not wasted: it is the line for the AC or geyser you add later.

Which size goes where follows the wire amps chart: 1.5 sq mm (13 A in a pipe, 10 A MCB) for lights, fans and 6 A sockets; 2.5 sq mm (18 A, 16 A MCB) for 16 A sockets, the kitchen, the geyser (16 A double-pole MCB, as CPWD's wiring specification recommends for water heaters) and an AC up to 12 A; 4 sq mm (24 A, 20 A MCB) only for an AC of 12–16 A. Which MCB on which line: which MCB for which load.

The thing most lists miss

A coil is 90 m of wire, not 90 m of wiring

Every run of pipe carries three wires of the same size. So the metres of wire are three times the metres of pipe, and the coils have to be bought in three colours.

Three wires in one pipe A switchboard on the left and a ceiling light on the right, joined by a 6 metre pipe holding a red, a black and a green wire. Below: 6 m of pipe takes 18 m of wire. Then three coils of 90 m, red, black and green, make 90 m of circuit, not 270. board light 6 m of pipe = 18 m of wire 6 m red + 6 m black + 6 m green 3 × 90 m = 270 m 90 m of circuit
Earth the same size as phase: IS 732 (standard figure). Colours red, black and green are among the seven V-Guard makes Classo+ in.

Buy by colour, not by total

"Four coils of 1.5" means nothing to an electrician until he knows which colours. Each colour has to cover its third of the run. That is why the counter below gives every size as red, black and green.

The green wire is not optional

Every socket and every metal fitting gets an earth wire, the same size as its phase: 2.5 sq mm earth on a 2.5 sq mm line. We count earth to every point. Leaving it out saves a coil and leaves the house without protection. More in earthing basics.

A few metres over is fine

The counter adds 10% spare. If one colour comes out up to 8 m over a whole coil, it doesn't add a coil: those metres come out of the spare. More than that, it adds one.

Which colour does which job, and why yellow or blue can also carry phase: phase, neutral and earth colours.

How we count

Points, boards and runs from the board

No maker publishes metres per room, so these are usual practice in Muzaffarpur houses: pipe in the slab and the walls, one distribution board (DB) on the ground floor near the meter. Each length is pipe; wire is three times it.

Where the wire runs in a two-floor house Cross-section of a two-floor house. The meter outside feeds the DB on the ground floor with 10 m of main wire. From the DB, each circuit runs about 5 m to the first switchboard, plus 3.5 m for each floor up. Each light, fan or socket is about 3 m from its board. Boards in the next room are 6 m apart. The AC has its own line, about 10 m plus 3.5 m per floor. The 16 A socket runs on 2.5 sq mm. FIRST FLOOR GROUND meter DB 10 m 3 m a point 6 m 16 A socket, 2.5 AC AC: own line, 10 m + 3.5 5 m + 3.5 m per floor — — circuit from the DB to a board (1.5) ━ own line on 2.5 sq mm Lengths are pipe. Wire = 3 × pipe, + 10% spare.
Drawn for one room per floor to keep it readable. Every room adds one board and its points; every floor adds 3.5 m to each run that climbs to it.
3 mof pipe
Each light, fan or 6 A socket from its boardA room has 5 such points, a kitchen 3, a bathroom 2, and each floor 3 more for the stairs, veranda and gate. 1.5 sq mm.
6 mper board
Board to board on the floorThe light circuit and the 6 A socket circuit loop from room to room; 3 m for a bathroom switch outside its door.
5 m+ 3.5 / floor
Each circuit from the DB to its floorTwo 1.5 sq mm circuits per floor (lights and fans, 6 A sockets), one 2.5 sq mm room power circuit, and the kitchen on its own.
6 mper socket
16 A socketsOne per room on the room power circuit; three in the kitchen (fridge, mixer, microwave or RO), 3 m apart. 2.5 sq mm.
10 m+ 3.5 / floor
AC and geyser: own line eachStraight from the DB, 2.5 sq mm. An AC whose plate shows 12–16 A goes on 4 sq mm. Water pump: 15 m.
10 mmain
Meter to DBPhase, neutral and earth, 4 sq mm; 6 sq mm if there is an AC now or later (as on the MCB page).
Each floor up

The same floor costs more wire the higher it is

Take one floor plan: 2 rooms, a bathroom, an AC and a geyser. Every circuit on it starts at the DB downstairs, so each floor up adds a climb to every run.

231 m+ 122 m
On the ground floor231 m of 1.5 sq mm and 122 m of 2.5 sq mm, spare included.
254 m+ 157 m
On the first floorAbout 23 m more 1.5 sq mm and 35 m more 2.5 sq mm than the same rooms downstairs.
277 m+ 191 m
On the second floorAnother 23 m and 34 m. The AC and geyser lines climb two floors each.
Sub-board?option
A small DB on each floorSome electricians put a sub-DB upstairs, fed by one thick line from below. It saves wire on the climbs but that one line must carry the whole floor, ACs and geyser included, which is often more than 4 sq mm's 20 A. Send us the floor's load before choosing it.

Building one floor now and one later? Lay the pipe for the upper floor's runs while the ground floor is being done, and pull its wire when you build. Pipe in a slab goes in before the casting: conduit before slab casting · fan box before casting.

Count your own house

Rooms, ACs and floors in, coils by colour out

Put in each floor as it will be finished. Leave a floor at zero if you are not building it. The lengths behind it are the ones listed above.

RoomsKitchenBathsACsGeysers Groundfloor Firstfloor Secondfloor

Room = bedroom or hall: 2 lights, a fan, two 6 A sockets and one 16 A socket. Most 1 and 1.5-ton splits show 12 A or less on the plate. Hall with two fans, or extra sockets? Count it as a room and a half by adding a room on that floor.

What to buy

1.5 sq mm——
2.5 sq mm——
4 sq mm for the AC——
Main, meter to DB——
Pipe and boxes
Boxes——
Board
MCBs——
Send me this list on WhatsApp

Typical figures from usual-practice lengths, with 10% spare; your electrician's point list decides. Coils: Classo+ 90 m. Switches, sockets, plates and the DB box are on the whole-house wiring kit; run lengths and voltage drop in the wiring calculator. Price: Ask rate.

What we see go wrong

Four buying mistakes

Buying a total, not colours

You see: two red coils, no black left

Five coils of one colour don't wire anything. Each size is bought as red, black and green, about a third each.

Thin earth, or none

You see: one green coil of 1 sq mm for the whole house

Earth is the same size as the phase beside it (IS 732). A 2.5 sq mm socket line has a 2.5 sq mm green.

Kitchen on 1.5 sq mm

You see: a warm socket behind the fridge

Fridge, mixer and microwave go on 16 A sockets and 2.5 sq mm. 1.5 is for lights, fans and 6 A sockets only.

Short coils

You see: "90 m" that runs out early

Check the length seal and the size printed along the wire before the coil is opened. Classo+ carries a "90 m assured" seal. More: real or fake wire.

Questions people ask us

Short answers

How many wire coils for a 2-room house? (2 kamre ke ghar mein kitne bundle)

Typically six 90 m coils: one red, one black and one green of 1.5 sq mm, and the same of 2.5 sq mm, for 2 rooms, a kitchen and a bathroom with one AC, a geyser and a pump. Plus about 33 m of 6 sq mm main from the meter.

How much wire for a 1,000 sq ft house?

Square feet alone don't decide it; rooms, points and floors do. A 1,000 sq ft single floor with 3 rooms, a kitchen and 2 baths comes to about 380 m of 1.5 sq mm and 240 m of 2.5 sq mm on our count: 9 coils. Online rules of thumb run from about 300 m to over 800 m for the same area, which is why we count points instead.

Why do I need three coils of each size?

Every run carries a phase (red), a neutral (black) and an earth (green) of the same size. Each colour covers its own third, so the smallest you can buy for one size is one coil of each colour.

Can the earth wire be thinner than the phase?

Not in house wiring: IS 732 takes the earth wire the same size as the phase up to 16 sq mm. 2.5 sq mm line, 2.5 sq mm green.

Should lights be on 1 sq mm or 1.5 sq mm?

1 sq mm (11 A in a pipe) can feed a light or fan point from its board. We count 1.5 sq mm (13 A) for the whole light circuit: one size, fewer coils of different sizes, and room for more points later. See the wire amps chart.

Do I buy all the wire at once?

Pipe and boxes go in first, at the slab and before plaster; wire is pulled after plaster. Buy the pipe at the slab stage and the wire when the walls are plastered, from the same list.

Is a coil really 90 m?

It should be. Classo+ coils carry V-Guard's "90 m assured" seal, and the size and BIS mark are printed along the wire. Check both before the coil is opened.

Sashikesh Kumar
Diploma in Electrical, Tashya Ventures

Looks after wires, switchgear, inverters and pumps at our Reva Road store, Muzaffarpur. The lengths on this page are usual practice for houses here, counted point by point; the wire sizes follow V-Guard's own Classo+ table, as on our wire amps chart.

Where the numbers come from

  1. V-Guard, Classo+ house wire product page: sizes 0.75 to 4 sq mm; colours red, yellow, blue, black, green, grey and white; "90 m assured" seal; in-conduit current 1.5 sq mm 13 A, 2.5 sq mm 18 A, 4 sq mm 24 A.
  2. IS 732 wiring code (standard figure): earth conductor the same size as the phase up to 16 sq mm.
  3. Lengths per point, per board, per floor (3 m, 6 m, 5 m + 3.5 m per floor, 10 m for AC, geyser and main, 15 m for the pump) and 10% spare: usual practice, Tashya Ventures electrical counter, Muzaffarpur. Pipe sizes 20 mm (light runs) and 25 mm (power runs and main): usual practice.
  4. Main wire 4 or 6 sq mm and MCB list: our which MCB for which load page.

Send us your room list

Rooms, ACs and floors, or a photo of the electrician's point list. We'll send back coils by size and colour, pipe, boxes and MCBs, with today's price, on WhatsApp.